Sample Fire Alarm Inspection Report (Redacted Format)

This sample shows how Oklahoma Secured organizes a written fire alarm inspection report so a facility owner can see what was tested, what the results were and what happens next. SAMPLE FORMAT: This is an illustrative example created by Oklahoma Secured to show how an inspection report is organized. The facility, people, dates, devices and results are fictional. It is not a report from a real customer or a completed job.

Illustrative sampleFictional facilityODOL AC441210

About this sample

SAMPLE FORMAT: This is an illustrative example created by Oklahoma Secured to show how an inspection report is organized. The facility, people, dates, devices and results are fictional. It is not a report from a real customer or a completed job.

Real reports identify the actual building, devices, dates and technician. Contact details, addresses and security-sensitive information are redacted here. Required inspection and testing activities depend on the applicable standard, adopted requirements and your authority having jurisdiction; this sample does not set them.

1. Report summary

Scroll sideways to see the full table →

Report summary
ItemEntry
FacilitySample Elementary School (fictional)
Address[Redacted]
Systems coveredOne addressable fire alarm control panel; Building A and Building B
Date of visit[Example date]
Inspection scopeVisual inspection and functional testing of the devices listed below, with the monitoring signal test coordinated through the facility's monitoring company
Facility contact[Name redacted]
Technician[Name and license number redacted]
Edition and requirements confirmed with AHJ[To be confirmed with the authority having jurisdiction for the actual facility]

2. Device results

Every device or function tested is listed with a unique identifier, location, what was done and a result. Results use four plain categories: Pass, Deficiency, Inaccessible and Not tested.

Scroll sideways to see the full table →

Device results (example)
IDLocationDeviceWhat was doneResultNotes
A-01Main entrance lobbyManual pull stationOperated; panel indicated alarmPass—
A-14Corridor 2, above doorSmoke detectorTested with listed test methodPass—
A-22Room 112 ceilingSmoke detectorTested with listed test methodDeficiencyDetector did not initiate alarm; recommend replacement. Repair quoted separately.
A-31Corridor 2Horn/strobeAudible and visible output observedPass—
A-38Gym storage roomHeat detectorNot testedInaccessibleRoom locked; facility contact unavailable. Retest to be scheduled.
B-05Mechanical roomDuct detectorTested; air handler shutdown interface observedPass—
B-09CafeteriaHorn/strobeStrobe did not flashDeficiencyAppliance replacement recommended.
PNLControl panel, Building APanel, battery and power supplyPanel functions and trouble signals reviewed; battery condition recordedPassBattery age recorded for owner planning.
MONMonitoringSignal transmission testTest signals sent in coordination with the monitoring companyPassReceipt confirmed by monitoring company.

3. Deficiency and follow-up register

Each deficiency is tied to a device and a next step, and stays open until completion evidence and a retest result are recorded. A repair quote is a separate document from the inspection report.

Scroll sideways to see the full table →

Deficiency register (example)
RefDevice and locationFindingRecommended actionStatus
D-1A-22 smoke detector, Room 112Did not initiate alarmReplace detector and retestOpen
D-2B-09 horn/strobe, cafeteriaStrobe did not flashReplace appliance and retestOpen
D-3A-38 heat detector, gym storageNot tested: accessGain access and testOpen

4. Items the owner should keep

  • The signed report, filed by building and date
  • Repair and retest records for each deficiency
  • Updated device list and as-built drawings when changes are made
  • Monitoring account contacts and test confirmation
  • The next scheduled inspection date, confirmed with the applicable authority

5. Limits of an inspection report

An inspection documents conditions at the time of the visit. It is not an approved design, an acceptance test or a guarantee that a system will operate in a future event. Any impairment or trouble condition should be handled under the facility's procedures.

Schedule Fire Alarm Testing

6. Download

Download the same sample as a PDF: Sample fire alarm inspection report (PDF).

Frequently Asked Questions

Is this a real customer report?
No. It is an illustrative sample with a fictional facility and fictional results, made to show the format. Real reports are specific to your building and are never published without the customer's permission.
What will my report include?
The building and system covered, what was tested, observed results by device, deficiencies, any inaccessible or untested items, and recommended next steps. Repair quotes are separate.
Does the report say which code edition applies?
The applicable edition and requirements depend on your facility and your authority having jurisdiction. Confirm them with your AHJ; Oklahoma's adoption of the 2024 IFC took effect September 14, 2026.

Educational information only. Confirm project-specific requirements with the applicable authority and qualified design professional.