About this sample
SAMPLE FORMAT: This is an illustrative example created by Oklahoma Secured to show how an inspection report is organized. The facility, people, dates, devices and results are fictional. It is not a report from a real customer or a completed job.
Real reports identify the actual building, devices, dates and technician. Contact details, addresses and security-sensitive information are redacted here. Required inspection and testing activities depend on the applicable standard, adopted requirements and your authority having jurisdiction; this sample does not set them.
1. Report summary
Scroll sideways to see the full table →
| Item | Entry |
|---|---|
| Facility | Sample Elementary School (fictional) |
| Address | [Redacted] |
| Systems covered | One addressable fire alarm control panel; Building A and Building B |
| Date of visit | [Example date] |
| Inspection scope | Visual inspection and functional testing of the devices listed below, with the monitoring signal test coordinated through the facility's monitoring company |
| Facility contact | [Name redacted] |
| Technician | [Name and license number redacted] |
| Edition and requirements confirmed with AHJ | [To be confirmed with the authority having jurisdiction for the actual facility] |
2. Device results
Every device or function tested is listed with a unique identifier, location, what was done and a result. Results use four plain categories: Pass, Deficiency, Inaccessible and Not tested.
Scroll sideways to see the full table →
| ID | Location | Device | What was done | Result | Notes |
|---|---|---|---|---|---|
| A-01 | Main entrance lobby | Manual pull station | Operated; panel indicated alarm | Pass | — |
| A-14 | Corridor 2, above door | Smoke detector | Tested with listed test method | Pass | — |
| A-22 | Room 112 ceiling | Smoke detector | Tested with listed test method | Deficiency | Detector did not initiate alarm; recommend replacement. Repair quoted separately. |
| A-31 | Corridor 2 | Horn/strobe | Audible and visible output observed | Pass | — |
| A-38 | Gym storage room | Heat detector | Not tested | Inaccessible | Room locked; facility contact unavailable. Retest to be scheduled. |
| B-05 | Mechanical room | Duct detector | Tested; air handler shutdown interface observed | Pass | — |
| B-09 | Cafeteria | Horn/strobe | Strobe did not flash | Deficiency | Appliance replacement recommended. |
| PNL | Control panel, Building A | Panel, battery and power supply | Panel functions and trouble signals reviewed; battery condition recorded | Pass | Battery age recorded for owner planning. |
| MON | Monitoring | Signal transmission test | Test signals sent in coordination with the monitoring company | Pass | Receipt confirmed by monitoring company. |
3. Deficiency and follow-up register
Each deficiency is tied to a device and a next step, and stays open until completion evidence and a retest result are recorded. A repair quote is a separate document from the inspection report.
Scroll sideways to see the full table →
| Ref | Device and location | Finding | Recommended action | Status |
|---|---|---|---|---|
| D-1 | A-22 smoke detector, Room 112 | Did not initiate alarm | Replace detector and retest | Open |
| D-2 | B-09 horn/strobe, cafeteria | Strobe did not flash | Replace appliance and retest | Open |
| D-3 | A-38 heat detector, gym storage | Not tested: access | Gain access and test | Open |
4. Items the owner should keep
- The signed report, filed by building and date
- Repair and retest records for each deficiency
- Updated device list and as-built drawings when changes are made
- Monitoring account contacts and test confirmation
- The next scheduled inspection date, confirmed with the applicable authority
5. Limits of an inspection report